System settings (Service menu – Settings)
Logamatic EMS RC35 programming unit - Subject to technical modifications
26
6
6.2 Boiler data
B Turn rotary selector anti-clockwise until boiler data is selected.
B Press to select boiler data.
The menu SETTINGS\BOILER is opened.
Menu item Input range
Factory
setting
Other information
Boiler pump after-run time
after burner stops?
deactivated,
1 to 60 min,
24 h
5 min Setting only possible with boilers with
internal pump.
1)
1) Not possible or not available with boilers with UBA1.x.
Set the pump logic
temperature:
0 to 65 °C 47 °C Setting only possible in conjunction
with BRM10.
Tab. 11 Navigator for service menu SETTINGS\BOILER
SERVICE\SETTINGS
B
plant data
boiler data
domestic hot water
heating circuit 1